The Basler Electric BE1-25A Automatic Synchronizer is a microprocessor-based system designed for precise generator synchronization to a power system. It automatically adjusts the incoming generator’s speed and phase to match the system, ensuring a smooth, transient-free connection by minimizing differences in speed, voltage, and phase angle at the moment of circuit breaker closure. This unit is engineered to reduce stress on equipment and enhance system stability, operating effectively with a wide range of prime movers, from slow-responding hydroturbines to fast-responding gas and diesel engines. The BE1-25A calculates an anticipatory close signal based on the breaker’s closing time and the measured slip frequency, ensuring the breaker contacts close when the phase angle is near zero.
### Technical Specifications
**Synchronization Parameters:**
* **Voltage Magnitude:** Adjustable limits to ensure generator voltage is within acceptable range of system voltage.
* **Slip Frequency:** Operates over a wide range, allowing compatibility with various prime mover types.
* **Phase Difference:** Closes breaker when phase angle between generator and bus is near zero.
* **Advance Angle Calculation:** Computes an advance angle based on preset breaker closing time and measured slip frequency for anticipatory closure.
**Operational Features:**
* **Microprocessor-Based System:** Enables sophisticated control and configuration.
* **Anticipatory Close Signal:** Provides smooth synchronizing with minimal system impact.
* **Multi-Generator Operation:** Capable of controlling multiple generators by recalling different breaker closing parameters from non-volatile memory for up to six systems.
* **Test Module:** Facilitates testing via front panel terminals.
* **Solid-State Design:** Ensures accurate, repeatable, and reliable operation.
* **User Interface:** Simple Human-Machine Interface (HMI) for intuitive settings configuration without a computer.
**Electrical Specifications:**
* **Power Supply:**
* 90-132 Vac, 50/60 Hz (single phase)
* 70-150 Vdc
* Burden: Less than 20.0 VA
* **Voltage Sensing Inputs:**
* 70-150 Vac, 50/60 Hz
* Burden: Less than 6 VA for generator input, less than 2 VA for bus input
* **Contact Sensing Inputs:**
* Minimum Rating: 0.05 A at 250 Vdc
* **Breaker Closing Output Contacts:**
* Make and carry 30 A at 250 Vdc for 1 second
* 7 A continuously
* Break 0.3 A at 250 Vdc (L/R = 0.04)
* **Lockout Output Contacts:**
* Make and break 5 A at 250 Vac (80% PF)
* Make and break 5 A at 28 Vdc (resistive)
* Make and break 0.5 A at 120 Vdc (resistive)
**Optional Modules:**
* **Voltage Acceptance Module (e.g., A1, A2):**
* Ensures generator voltage is within preselected magnitude relative to bus voltage before breaker closure.
* A2 option defines high and low bus voltage and voltage difference parameters.
* Can use up to three voltage parameters to constrain breaker command signals.
* Prerequisite for voltage matching options.
* **Frequency Matching Module (e.g., F5):**
* Provides proportional pulsed contact output for adjusting generator speed.
* Facilitates fast, reliable frequency matching with patented real-time adaptive proportional speed control algorithm, eliminating overshoots and hunting.
* **Voltage Matching Module (e.g., V1):**
* Provides continuous closed contact for adjusting generator voltage.
* Delivers raise and lower signals to the generator’s voltage regulator.
* **Dead Bus Module (e.g., D1):**
* Enables immediate breaker closing when a dead bus condition is sensed.
* Allows breaker closing without synchronization for black start capability.
**Physical Specifications:**
* **Enclosure:** Standard 19-inch rack-mounted case with a front cover.
* **Weight:** Not specified.
**Environmental Specifications:**
* **Operating Temperature:** -40°C to 70°C (-40°F to 158°F)
**Certifications and Compliance:**
* Qualified to ANSI/IEEE C37.
* CSA certified, UL listed, CE qualified.
* Tested for interference in accordance with IEC C37.90-1989.
* Maintains proper operation when tested for interference in accordance with IEC C37.90-1989, Trial-Use Standard Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceivers.
* Standard Surge Withstand Capability Tests (Oscillatory and Fast Transient) per IEC 255-5 Impulse Test and Dielectric Test.
* Patented in the US, 1998, Patent No. 5761073.
### Why Choose Aumictech for Basler Electric BE1-25A Automatic Synchronizer?
At Aumictech, we specialize in supplying high-end power system automation equipment. Whether you need precise generator synchronization, enhanced system stability, or robust protection for your rotating machinery, our team ensures the Basler Electric BE1-25A Automatic Synchronizer delivers maximum performance for your critical applications.