The Fluke 1587FC is a dual-function handheld instrument combining digital insulation testing with True RMS multimeter capabilities. It measures insulation resistance from 0.01 MΩ to 2 GΩ across five selectable test voltages (50 V, 100 V, 250 V, 500 V, 1000 V) and performs comprehensive electrical diagnostics on circuits up to 1000 V. Live circuit detection prevents unsafe testing, while auto-discharge protects users from residual capacitive voltage. The multimeter function covers AC/DC voltage (0 mV to 1000 V), current to 400 mA, resistance to 50 MΩ, capacitance to 9999 µF, temperature from -40 °C to 537 °C, and frequency up to 99.99 kHz. PI/DAR timed ratio tests with TrendIt™ graphing accelerate diagnosis of moisture and contamination in insulation systems. Fluke Connect Measurements app integration enables wireless data sharing, remote monitoring, and historical measurement tracking for enhanced field diagnostics and documentation.
– Technical Specifications
Insulation Testing
• Measurement range: 0.01 MΩ to 2 GΩ
• Test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
• Test voltage accuracy: +20%, -0%
• Short-circuit test current: 1 mA nominal
• Live circuit detection: Inhibits testing if terminal voltage > 30 V
• Auto-discharge: Capacitive voltage protection
• PI/DAR ratio tests: Supported with TrendIt™ graphs
• Maximum capacitive load: 1 µF
Digital Multimeter Functions
• DC voltage: 600.0 mV to 1000 V, accuracy ±(0.09% + 2)
• AC voltage: 600.0 mV to 600.0 V, accuracy ±(1% + 3) at 50–60 Hz
• DC millivolts: 600.0 mV range, resolution 0.1 mV, accuracy ±(0.1% + 1)
• AC/DC current: 0–400 mA (600 mA overload for 2 minutes), accuracy ±(0.2% + 2) DC
• Resistance: 0.1 Ω to 50 MΩ
• Continuity: Audible tone below 25 Ω
• Capacitance: 1 nF to 9999 µF, accuracy ±(1.2% ± 90 counts)
• Diode test: 0.6 V at 1.0 mA nominal current
• Temperature: -40 °C to 537 °C, resolution 0.1 °C
• Frequency: 0.01 Hz to 99.99 kHz, accuracy ±(0.1% + 1)
• Input impedance (DC voltage): 10 MΩ nominal
– Key Features
• Large backlit display
• Fluke Connect™ wireless connectivity
• Min/Max measurement recording
• Reading smoothing for reduced display fluctuations
– Typical Applications
Insulation condition assessment, preventative maintenance, motor and cable diagnostics, electrical troubleshooting, condition-based monitoring with cloud-based data tracking.