The HP/Agilent 10020A Resistive Divider Probe Kit is a precision signal probing system engineered for measuring fast-transition-time signals within high-impedance circuits. It integrates directly with 50 Ω oscilloscope inputs and extends compatibility to non-50 Ω systems when paired with a 50 Ω feedthrough termination such as the Agilent 10100C. The probe kit delivers low input resistance and minimal capacitance, ensuring high-fidelity signal acquisition across diverse measurement applications.
– Technical Specifications
• Type: Resistive Divider Probe Kit
• Bandwidth: Approximately 700 MHz
• Input Capacitance: Less than 0.7 pF (50 Ω terminated)
• Attenuation Ratios and Input Impedance (50 Ω terminated):
– 1:1 at 50 Ω
– 5:1 at 260 Ω
– 10:1 at 500 Ω
– 20:1 at 1000 Ω
– 50:1 at 2500 Ω
– 100:1 at 5000 Ω
• Division Accuracy: ±3% (10:1 and 100:1 attenuation, 50 Ω terminated)
• Cable Length: Approximately 1.2 m (4 ft) standard; 9 ft stiff Teflon cable available (Option 001)
• Output Connector: BNC
• Weight: 0.45 kg (1 lb)
– Key Features
• Low input RC characteristics minimize circuit loading and preserve signal integrity
• Multiple attenuation ratios (1:1 through 100:1) support varied measurement scales
• Accurate division performance requires proper 50 Ω termination
• Compact form factor at 0.45 kg facilitates bench-top and field deployments
– Typical Applications
• Signal tracing in high-impedance circuits
• Waveform analysis of fast-transition signals
• Component testing requiring minimal loading effects
– Compatibility & Integration
The 10020A operates with 50 Ω input oscilloscopes. For non-50 Ω systems, integrate the Agilent 10100C or 10100A 50 Ω feedthrough termination. Complementary accessories include the Agilent 10240B Blocking Capacitor for AC coupling, Agilent 10218A BNC Adapter, 6-32 Adapter Tip for probe tip kits (10036A, 10037A), Spanner Tip for minimized ground lead inductance, and Agilent 10229A Hook Tip Adapter.