The Lytron RC022 is a recirculating chiller from the Kodiak series engineered to maintain precise fluid temperatures in laboratory, industrial, and specialized processing environments. Operating with 2400 W (8.2 kBTU/Hr) cooling capacity at 60 Hz with 20°C ambient and setpoint conditions, this unit delivers ±0.1°C temperature stability across a coolant range of +5°C to +35°C. The compact 376 × 623 × 673 mm footprint houses an 8-liter reservoir with 1/2 and 3/4 inch FNPT connections, accommodating multiple pump configurations from 0.5 gpm (1.9 lpm) flow rates.
– Technical Specifications
• Cooling capacity: 2400 W (8.2 kBTU/Hr) at 60 Hz, 20°C ambient, 20°C setpoint
• Temperature stability: ±0.1°C
• Coolant temperature range: +5°C to +35°C (41°F to 95°F)
• Ambient temperature range: +10°C to +35°C (50°F to 95°F)
• Reservoir capacity: 8 liters (2 gallons)
• Fluid connections: 1/2, 3/4 inch FNPT
• Pump options: PDP, Centrifugal, and Turbine configurations; minimum flow capacity 0.5 gpm (1.9 lpm)
• Dimensions (W × D × H): 376 × 623 × 673 mm (14.8 × 24.5 × 26.5 inches)
• Available in air-cooled and water-cooled versions
– Key Features
• Microprocessor temperature controller with 0.1°C setpoint resolution and digital display
• °C/°F selectable display
• Low flow shut-off and auto-restart capability
• Configurable relay contacts (normally open or normally closed)
• Digital pressure sensing
• Low-level, low/high temperature fault detection with audible alarm and mute function
• Calibration offset and fault shut-off toggle
• Remote start support
• Optional RS-232 interface for external communication
• Vibration isolation for compressor and pump operation
– Typical Applications
Laboratory cooling systems, industrial process temperature control, and specialized equipment requiring stable thermal management.
– Compatibility & Integration
Two electrical configurations available: 230V 50 Hz single phase (9.5 FLA) or 208/230V 60 Hz single phase (10.0 FLA). Use filtered clean water above 10°C/50°F; freezing-point depressant (ethylene glycol) required for setpoints at or below 10°C/50°F. Automotive antifreeze is not recommended.