The Minco CT16 is a compact 1/16th DIN microprocessor-based temperature and process controller delivering precise regulation across on/off, proportional, and PID control modes. This single-input, single-output platform accepts universal sensor inputs—thermocouple, RTD, and current—making it adaptable to diverse industrial and laboratory temperature management systems. The CT16A2 provides fixed operation, while the CT16A3 adds auto/manual switching capability. Built for harsh environments, it operates reliably from -10°C to 55°C ambient and draws power from 100–240 VAC or 132–240 VDC supplies.
– Technical Specifications
• Enclosure: 1/16th DIN form factor; 1.89″ × 1.89″ × 5.24″ (maximum)
• Sensor Input: Universal; supports thermocouple, RTD, and current signals (single input)
• Control Modes: On/Off, Proportional, PID; Auto/Manual operation (CT16A3 only)
• Power Supply: 100–240 VAC or 132–240 VDC
• Alarm Output: 1 × 3A @ 240 VAC relay
• Control Output: 1 × 2A @ 240 VAC solid-state or 1 × 15V @ 20 mA voltage output
• Operating Ambient: -10°C to 55°C
• Certifications: UL, cUL, CE
– Key Features
• Universal sensor compatibility eliminates input module swapping
• Dual-model architecture supports both fixed and flexible control strategies
• Multi-output flexibility: relay, solid-state, or analog voltage configurations
• Optional serial communications (RS-485 or RS-232) enable remote parameter access and system integration
• Analog retransmission outputs (0–20 mAdc or 0–10 Vdc, scalable) mirror process variable or set point to external instrumentation
• Four-stage set point selection via contact closure for rapid process switching
• Analog remote set point control accepts 0–10 VDC, 0/4–20 mAdc, or 0–10,000 Ω inputs
– Typical Applications
Process heating, thermal chamber regulation, oven control, fluid temperature management, and any industrial or OEM system requiring single-loop temperature stabilization with configurable control algorithms.
– Compatibility & Integration
RS-485 and RS-232 serial interfaces support networked deployment and supervisory control. Analog retransmission options bridge to SCADA, PLC, and data acquisition systems. Multi-input remote set point modes accommodate analog sensor feedback and external command signals.