The NI FP-DO-DC60 is a two-channel discrete output module for FieldPoint terminal bases, engineered to switch and control DC loads from 3 to 60 VDC in industrial automation and process control systems. Each channel delivers 0.75 A at 25°C (0.3 A at 60°C) with a maximum output delay of 0.06 ms, supporting both sinking and sourcing device topologies. The module integrates channel-to-channel optical isolation and 2500 V isolation from the power supply and backplane, ensuring safe operation in electrically noisy environments. Two independent replaceable fuses and dual green status LEDs provide fault visibility and circuit protection.
Technical Specifications
• Output Channels: 2 discrete DC outputs
• Voltage Rating: 3–60 VDC
• Current Per Channel: 0.75 A @ 25°C; 0.3 A @ 60°C
• Voltage Drop: 1.3 V @ 0.75 A
• Maximum Output Delay: 0.06 ms
• Scan Time: 0.2 ms
• Power Consumption: 70 mW
• Isolation: Channel-to-channel optical isolation; 2500 V isolation from power supply and backplane
• Field Wiring: 24 to 12 AWG
• Operating Temperature: −40 to 70 °C
• Storage Temperature: −55 to 85 °C
• Relative Humidity: 10 to 90% non-condensing
• Weight: 2.1 oz
– Key Features
• Two independent output channels with individual fuses and status indicators
• Fast output response with 0.06 ms maximum delay
• Optical isolation protects against ground loops and transients
• Wide voltage range accommodates diverse DC control requirements
• Replaceable fuses enable field maintenance without module replacement
– Typical Applications
• Solenoid and relay control in process automation
• Discrete load switching in remote terminal applications
• Industrial device activation and shutdown sequences
• Equipment interlocking and safety circuits
– Compatibility & Integration
The FP-DO-DC60 mounts directly to the FP-TB-10 terminal base, which accommodates up to six modules. A single network interface module can control up to 9 FP-TB-10 bases. The C and V power bus terminals on the FP-TB-10 support external power supply connection when channel isolation is not required.